<< Click to Display Table of Contents >>
How to Configure a Device from A Series Using an AJ71UC24 Adapter |
Before establishing communication, users must configure dip-switches and the Mode Setting switch according to the adapter to use, RS-232 or RS-485. For RS-232 connectors, the Mode Setting switch must be set to 1 (one, Protocol 1). For RS-485 connectors, the Mode Setting switch must be set to 5 (five, Protocol 1 for RS-485). Dip-switches must be configured according to the next tables.
Available options for Dip-Switches
Dip-Switch |
Position |
Notes |
|---|---|---|
SW-11 |
OFF |
|
SW-12 |
ON |
8 (eight) bits per character |
SW-13 |
|
Please check the next table |
SW-14 |
|
Please check the next table |
SW-15 |
|
Please check the next table |
SW-16 |
ON |
Parity enabled |
SW-17 |
ON |
Even parity |
SW-18 |
OFF |
One stop bit |
SW-21 |
ON |
Checksum enabled |
SW-22 |
ON |
Writing during execution enabled |
SW-23 |
ON |
Computer link |
SW-24 |
OFF |
Not used |
Baud rate configuration for SW-13, SW-14, and SW-15 Switches
Baud Rate |
SW-13 |
SW-14 |
SW-15 |
|---|---|---|---|
2400 |
ON |
ON |
OFF |
4800 |
OFF |
OFF |
ON |
9600 |
ON |
OFF |
ON |
19200 |
OFF |
ON |
ON |