<< Click to Display Table of Contents >>
Tag Reference |
The next tables contain reference values and commands supported by PLC and Block Tags of this Driver.
Description |
Minimum value |
Maximum Value |
|---|---|---|
Number of modules per unit |
1 (one) |
5 (five) |
Reference channels of a unit |
1 (one) |
60 |
Calculation channels of a unit |
1 (one) |
60 |
Left or right span |
0 (zero) |
30000 |
Left or right scale of channels |
-30000 |
30000 |
Position of decimal place |
0 (zero) |
4 (four) |
Operation mode |
Possible values are 0: Operation, 1: Setup, or 2: Calibration |
|
Index |
Parameter |
Valid Interval |
|---|---|---|
0 |
20 mV |
-20.000 a 20.000 mV |
1 |
60 mV |
-60.00 a 60.00 mV |
2 |
200 mV |
-200.00 a 200.00 mV |
3 |
2 V |
-2.0000 a 2.0000 V |
4 |
6 V |
-6.000 a 6.000 V |
5 |
20 V |
-20.000 a 20.000 V |
6 |
50 V |
-50.00 a 50.00 V |
Index |
Description |
Parameter |
Valid Interval |
|---|---|---|---|
0 |
R |
R |
0.0 to 1760.0 ºC |
1 |
S |
S |
0.0 to 1760.0 ºC |
2 |
B |
B |
0.0 to 1820.0 ºC (precision in the junction compensation for a B type) |
3 |
K |
K |
-200.0 to 1370.0 ºC |
4 |
E |
E |
-200.0 to 800.0 ºC |
5 |
J |
J |
-200.0 to 1100.0 ºC |
6 |
T |
T |
-200.0 to 400.0 ºC |
7 |
N |
N |
0.0 to 1300.0 ºC |
8 |
W |
W |
0.0 to 2315.0 ºC |
9 |
L |
L |
-200.0 to 900.0 ºC |
10 |
U |
U |
-200.0 to 400.0 ºC |
11 |
KpAu7Fe |
KP |
0.0 to 300.0 K |
Detector of temperature by resistance (RTD)
Index |
Description |
Parameter |
Valid Interval |
|---|---|---|---|
0 |
Pt100: 1 mA |
PT1 |
-200.0 to 600.0 ºC |
1 |
Pt100: 2 mA |
PT2 |
-200.0 to 250.0 ºC |
2 |
JPt100: 1 mA |
JPT1 |
-200.0 to 550.0 ºC |
3 |
JPt100: 2 mA |
JPT2 |
-200.0 to 250.0 ºC |
4 |
Pt50: 2 mA |
PT50 |
-200.0 to 550.0 ºC |
5 |
Pt100: 1 mA-H |
PT1S |
-140.00 to 150.0 ºC |
6 |
Pt100: 2 mA-H |
PT2S |
-70.00 to 70.00 ºC |
7 |
JPt100: 1 mA-H |
JPT1S |
-140.00 to 150.00 ºC |
8 |
JPt100: 2 mA-H |
JPT2S |
-70.00 to 70.00 ºC |
9 |
Ni100: 1 mA-S (1) |
NI1 |
-200.0 to 250.0 ºC |
10 |
No100: 1 mA-D (RTD SAMA) |
NI2 |
-60.0 to 180.0 ºC |
11 |
Ni120: 1 mA (RTD DIN) |
NI3 |
-70.0 to 200.0 ºC |
12 |
Cu10: GE (RTD McGRAW EDISON COMPANY) |
CU1 |
-200.0 to 300.0 ºC |
13 |
Cu10: L&N |
CU2 |
-200.0 to 300.0 ºC |
14 |
Cu10: WEED (RTD McGRAW EDISON COMPANY) |
CU3 |
-200.0 to 300.0 ºC |
15 |
Cu10: BAILEY (RTD McGRAW EDISON COMPANY) |
CU4 |
-200.0 to 300.0 ºC |
16 |
J263*B |
J263B |
0.0 to 300.0 K |
NOTE |
The specific precision of the compensation interval of indexes 12 (Cu10: GE), 13 (Cu10: L&N), 14 (Cu10: WEED), and 15 (Cu10: BAILEY) is, respectively, -84.4 to 170.0 ºC, -75.0 to 150.0 ºC, -20.0 to 250.0 ºC, and -20.0 to 250.0 ºC. |
Index |
Parameter |
Valid Interval |
|---|---|---|
0 |
LEVL |
Possible values are 0: Off (< 2.4 V) or 1: On (>= 2.4 V) |
1 |
CONT |
Possible values are 0: Off or 1: On |
Index |
Parameter |
Valid Interval |
|---|---|---|
0 |
20 mA |
-20.000 to 20.000mA |
Power monitor (AC)
Index |
Parameter |
Valid Interval |
|---|---|---|
0 |
25V-0.5A |
25 VAC, 0.5 A |
1 |
25V-5A |
25 VAC, 5 A |
2 |
250V-0.5A |
250 VAC, 0.5 A |
3 |
250V-5A |
250 VAC, 5 A |
Measurement scales (sequence of previous table)
Index |
Parameter |
25V-0.5A |
25V-5A |
250V-0.5A |
250V-5A |
|---|---|---|---|---|---|
0 to 4 |
V1, V2, V3, V13, V0 |
0.00 to 25.00 Vrms |
0.00 to 25.00 Vrms |
0.0 to 250.0 Vrms |
0.0 to 250.0 Vrms |
5 to 9 |
I1, I2, I3, I13, I0 |
0.0000 to 0.5000 Arms |
0.0000 to 5.000 Arms |
0.0000 to 0.5000 Arms |
0.000 to 5.000 Arms |
10 to 12 |
P1, P2, P3 |
-12.50 to 12.50 W |
-125.0 to 125.0 W |
-125.0 to 125.0 W |
-1250 to 1250 W |
13 |
P13 |
-25.00 to 25.00 W |
-250.0 to 250.0 W |
-250.0 to 250.0 W |
-2500 to 2500 W |
14 |
P0 |
-37.50 to 37.50 W |
-375.0 to 375.0 W |
-375.0 to 375.0 W |
-3750 to 3750 W |
15 to 17 |
VA1, VA2, VA3 |
0.00 to 12.50 VA |
0.0 to 125.0 VA |
0.0 to 125.0 VA |
0 to 1250 VA |
18 |
VA13 |
0.00 to 25.00 VA |
0.0 to 250.0 VA |
0.0 to 250.0 VA |
0 to 2500 VA |
19 |
VA0 |
0.00 to 37.50 VA |
0.0 to 375.0 VA |
0.0 to 375.0 VA |
0 to 3750 VA |
20 to 22 |
Var1, Var2, Var3 |
0.00 to 12.50 Var |
0.0 to 125.0 Var |
0.0 to 125.0 Var |
0 to 1250 Var |
23 |
Var13 |
0.00 to 25.00 Var |
0.0 to 250.0 Var |
0.0 to 250.0 Var |
0 to 2500 Var |
24 |
Var0 |
0.00 to 37.50 Var |
0.0 to 375.0 Var |
0.0 to 375.0 Var |
0 to 3750 Var |
25 to 29 |
PF1, PF2, PF3, PF13, PF0 |
-1.00 to 1.00 |
-1.00 to 1.00 |
-1.00 to 1.00 |
-1.00 to 1.00 |
30 to 34 |
PH1, PH2, PH3, PH13, PH0 |
-80.0 to 80.0 deg |
-80.0 to 80.0 deg |
-80.0 to 80.0 deg |
-80.0 to 80.0 deg |
35 |
FREQ |
45.00 to 65.00 Hz |
45.00 to 65.00 Hz |
45.00 to 65.00 Hz |
45.00 to 65.00 Hz |
Index |
Parameter |
Valid Interval |
|---|---|---|
0 |
2k |
-2000 to 2000 με (bridge ¼) |
1 |
2k |
-1000 to 1000 με (bridge ½) |
2 |
2k |
-500 to 500 με (full bridge) |
3 |
20k |
-20000 to 20000 με (bridge ¼) |
4 |
20k |
-10000 to 10000 με (bridge ½) |
5 |
20k |
-5000 to 5000 με (full bridge) |
6 |
200k |
-200000 to 200000 με (bridge ¼) |
7 |
200k |
-100000 to 100000 με (bridge ½) |
9 |
200k |
-50000 to 50000 με (full bridge) |
Index |
Parameter |
Valid Interval |
|---|---|---|
0 |
RATE |
0 to 30000 |
1 |
GATE |
0 to 30000 |
General index to access input types
Index |
Table |
|---|---|
0 |
|
1 |
|
2 |
|
3 |
|
4 |
|
5 |
|
6 |
|
7 |
|
8 |
|
9 |
|
10 |
The rule for forming the addressing of channels is expressed by 3 (three) characters grouped in the order Unit + Slot + Slot Number.
NOTE |
When channel is equal to 10, add 1 (one) to the current slot value and configure the channel or relay with the value 0 (zero). |
Stand-alone or expansible architecture
Unit or Slot |
Slot 0 |
Slot 1 |
Slot 2 |
Slot 3 |
Slot 4 |
Slot 5 |
|---|---|---|---|---|---|---|
Unit [I | S | A] |
x01 to x10 |
x11 to x20 |
x21 to x30 |
x31 to x40 |
x41 to x50 |
x51 to x60 |
Unit 0: |
001 to 010 |
011 to 020 |
021 to 030 |
031 to 040 |
041 to 050 |
051 to 060 |
Unit 1: |
101 to 110 |
111 to 120 |
121 to 130 |
131 to 140 |
141 to 150 |
151 to 160 |
Unit 2: |
101 to 110 |
111 to 120 |
121 to 130 |
131 to 140 |
141 to 150 |
151 to 160 |
Unit 3: |
301 to 310 |
311 to 320 |
321 to 330 |
331 to 340 |
341 to 350 |
351 to 360 |
Unit 4: |
401 to 410 |
411 to 420 |
421 to 430 |
431 to 440 |
441 to 450 |
451 to 460 |
Unit 5: |
501 to 510 |
511 to 520 |
521 to 530 |
531 to 540 |
541 to 550 |
551 to 560 |
The value x on the first row of the previous table must be replaced by the respective letter of the unit. Possible values are I: Main unit, S: DI or DO type, or A: Calculation channel. Therefore, cross-referencing row and column allows knowing the valid addressing interval for a module. For example, to select unit 2 (two) and slot 2 (two) the addressing interval for a module is from 121 to 130.
Users can also address all channels from a unit. For example, the value Unit 3: addresses all channels, from 301 to 360. If this interval does not contain all modules, the DA100 module responds with intervals of addresses. The next table contains valid values for each architecture.
Values per architecture
|
Stand-Alone Unit |
Expansible Unit |
|---|---|---|
Unit |
0 (zero) |
I (DA100, main unit) and from 0 (zero) to 5 (five, sub-units DS400 or DS600) |
Slot |
0 (zero) to 5 (five) |
0 (zero) to 5 (five) |
Channel or relay |
1 (one) to 10. When the channel is equal to 10, add 1 (one) to the current value of the slot and configure the channel or relay with the value 0 (zero) |
1 (one) to 10.When the channel is equal to 10, add 1 (one) to the current value of the slot and configure the channel or relay with the value 0 (zero) |
The next table contains the valid intervals in Yokogawa DA100 Driver for the modules of each DA100 unit.
Unit |
Valid Range |
|---|---|
0 |
001 to 060 |
1 |
101 to 160 |
2 |
201 to 260 |
3 |
301 to 360 |
4 |
401 to 460 |
5 |
501 to 560 |
I |
601 to 660 |
S |
701 to 760 |
A |
801 to 860 |
The functionality of Yokogawa DA100 Driver commands are subdivided into the following groups:
•Effective commands: From 50 to 62
•Commands to control execution: From 100 to 104
•Commands to request data output: From 150 to 162