The next tables contain reference values and commands supported by PLC and Block Tags of this Driver.

Main references

Description

Minimum value

Maximum Value

Number of modules per unit

1 (one)

5 (five)

Reference channels of a unit

1 (one)

60

Calculation channels of a unit

1 (one)

60

Left or right span

0 (zero)

30000

Left or right scale of channels

-30000

30000

Position of decimal place

0 (zero)

4 (four)

Operation mode

Possible values are 0: Operation, 1: Setup, or 2: Calibration

 

Analog Parameters

Voltage input CC (Volt)

Index

Parameter

Valid Interval

0

20 mV

-20.000 a 20.000 mV

1

60 mV

-60.00 a 60.00 mV

2

200 mV

-200.00 a 200.00 mV

3

2 V

-2.0000 a 2.0000 V

4

6 V

-6.000 a 6.000 V

5

20 V

-20.000 a 20.000 V

6

50 V

-50.00 a 50.00 V

 

Thermocouple (TC, RRJC)

Index

Description

Parameter

Valid Interval

0

R

R

0.0 to 1760.0 ºC

1

S

S

0.0 to 1760.0 ºC

2

B

B

0.0 to 1820.0 ºC (precision in the junction compensation for a B type)

3

K

K

-200.0 to 1370.0 ºC

4

E

E

-200.0 to 800.0 ºC

5

J

J

-200.0 to 1100.0 ºC

6

T

T

-200.0 to 400.0 ºC

7

N

N

0.0 to 1300.0 ºC

8

W

W

0.0 to 2315.0 ºC

9

L

L

-200.0 to 900.0 ºC

10

U

U

-200.0 to 400.0 ºC

11

KpAu7Fe

KP

0.0 to 300.0 K

 

Detector of temperature by resistance (RTD)

Index

Description

Parameter

Valid Interval

0

Pt100: 1 mA

PT1

-200.0 to 600.0 ºC

1

Pt100: 2 mA

PT2

-200.0 to 250.0 ºC

2

JPt100: 1 mA

JPT1

-200.0 to 550.0 ºC

3

JPt100: 2 mA

JPT2

-200.0 to 250.0 ºC

4

Pt50: 2 mA

PT50

-200.0 to 550.0 ºC

5

Pt100: 1 mA-H

PT1S

-140.00 to 150.0 ºC

6

Pt100: 2 mA-H

PT2S

-70.00 to 70.00 ºC

7

JPt100: 1 mA-H

JPT1S

-140.00 to 150.00 ºC

8

JPt100: 2 mA-H

JPT2S

-70.00 to 70.00 ºC

9

Ni100: 1 mA-S (1)

NI1

-200.0 to 250.0 ºC

10

No100: 1 mA-D (RTD SAMA)

NI2

-60.0 to 180.0 ºC

11

Ni120: 1 mA (RTD DIN)

NI3

-70.0 to 200.0 ºC

12

Cu10: GE (RTD McGRAW EDISON COMPANY)

CU1

-200.0 to 300.0 ºC

13

Cu10: L&N

CU2

-200.0 to 300.0 ºC

14

Cu10: WEED (RTD McGRAW EDISON COMPANY)

CU3

-200.0 to 300.0 ºC

15

Cu10: BAILEY (RTD McGRAW EDISON COMPANY)

CU4

-200.0 to 300.0 ºC

16

J263*B

J263B

0.0 to 300.0 K

 

NOTE

The specific precision of the compensation interval of indexes 12 (Cu10: GE), 13 (Cu10: L&N), 14 (Cu10: WEED), and 15 (Cu10: BAILEY) is, respectively, -84.4 to 170.0 ºC, -75.0 to 150.0 ºC, -20.0 to 250.0 ºC, and -20.0 to 250.0 ºC.

 

Contact (DI)

Index

Parameter

Valid Interval

0

LEVL

Possible values are 0: Off (< 2.4 V) or 1: On (>= 2.4 V)

1

CONT

Possible values are 0: Off or 1: On

 

Current input CC (mA)

Index

Parameter

Valid Interval

0

20 mA

-20.000 to 20.000mA

 

Power monitor (AC)

Index

Parameter

Valid Interval

0

25V-0.5A

25 VAC, 0.5 A

1

25V-5A

25 VAC, 5 A

2

250V-0.5A

250 VAC, 0.5 A

3

250V-5A

250 VAC, 5 A

 

Measurement scales (sequence of previous table)

Index

Parameter

25V-0.5A

25V-5A

250V-0.5A

250V-5A

0 to 4

V1, V2, V3, V13, V0

0.00 to 25.00 Vrms

0.00 to 25.00 Vrms

0.0 to 250.0 Vrms

0.0 to 250.0 Vrms

5 to 9

I1, I2, I3, I13, I0

0.0000 to 0.5000 Arms

0.0000 to 5.000 Arms

0.0000 to 0.5000 Arms

0.000 to 5.000 Arms

10 to 12

P1, P2, P3

-12.50 to 12.50 W

-125.0 to 125.0 W

-125.0 to 125.0 W

-1250 to 1250 W

13

P13

-25.00 to 25.00 W

-250.0 to 250.0 W

-250.0 to 250.0 W

-2500 to 2500 W

14

P0

-37.50 to 37.50 W

-375.0 to 375.0 W

-375.0 to 375.0 W

-3750 to 3750 W

15 to 17

VA1, VA2, VA3

0.00 to 12.50 VA

0.0 to 125.0 VA

0.0 to 125.0 VA

0 to 1250 VA

18

VA13

0.00 to 25.00 VA

0.0 to 250.0 VA

0.0 to 250.0 VA

0 to 2500 VA

19

VA0

0.00 to 37.50 VA

0.0 to 375.0 VA

0.0 to 375.0 VA

0 to 3750 VA

20 to 22

Var1, Var2, Var3

0.00 to 12.50 Var

0.0 to 125.0 Var

0.0 to 125.0 Var

0 to 1250 Var

23

Var13

0.00 to 25.00 Var

0.0 to 250.0 Var

0.0 to 250.0 Var

0 to 2500 Var

24

Var0

0.00 to 37.50 Var

0.0 to 375.0 Var

0.0 to 375.0 Var

0 to 3750 Var

25 to 29

PF1, PF2, PF3, PF13, PF0

-1.00 to 1.00

-1.00 to 1.00

-1.00 to 1.00

-1.00 to 1.00

30 to 34

PH1, PH2, PH3, PH13, PH0

-80.0 to 80.0 deg

-80.0 to 80.0 deg

-80.0 to 80.0 deg

-80.0 to 80.0 deg

35

FREQ

45.00 to 65.00 Hz

45.00 to 65.00 Hz

45.00 to 65.00 Hz

45.00 to 65.00 Hz

 

Gauge input (STRAIN)

Index

Parameter

Valid Interval

0

2k

-2000 to 2000 με (bridge ¼)

1

2k

-1000 to 1000 με (bridge ½)

2

2k

-500 to 500 με (full bridge)

3

20k

-20000 to 20000 με (bridge ¼)

4

20k

-10000 to 10000 με (bridge ½)

5

20k

-5000 to 5000 με (full bridge)

6

200k

-200000 to 200000 με (bridge ¼)

7

200k

-100000 to 100000 με (bridge ½)

9

200k

-50000 to 50000 με (full bridge)

 

Pulse input (PULSE)

Index

Parameter

Valid Interval

0

RATE

0 to 30000

1

GATE

0 to 30000

 

General index to access input types

Index

Table

0

Voltage input CC

1

Thermocouple

2

Detector of temperature by resistance

3

Contact

4

Current input CC

5

Measurement scale 25V-0.5A

6

Measurement scale 25V-5A

7

Measurement scale 250V-0.5A

8

Measurement scale 250V-5A

9

Gauge input

10

Pulse input

 

Rule for Addressing Channels of DA100 Modules

The rule for forming the addressing of channels is expressed by 3 (three) characters grouped in the order Unit + Slot + Slot Number.

 

NOTE

When channel is equal to 10, add 1 (one) to the current slot value and configure the channel or relay with the value 0 (zero).

 

Stand-alone or expansible architecture

Unit or Slot

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Unit [I | S | A]

x01 to x10

x11 to x20

x21 to x30

x31 to x40

x41 to x50

x51 to x60

Unit 0:

001 to 010

011 to 020

021 to 030

031 to 040

041 to 050

051 to 060

Unit 1:

101 to 110

111 to 120

121 to 130

131 to 140

141 to 150

151 to 160

Unit 2:

101 to 110

111 to 120

121 to 130

131 to 140

141 to 150

151 to 160

Unit 3:

301 to 310

311 to 320

321 to 330

331 to 340

341 to 350

351 to 360

Unit 4:

401 to 410

411 to 420

421 to 430

431 to 440

441 to 450

451 to 460

Unit 5:

501 to 510

511 to 520

521 to 530

531 to 540

541 to 550

551 to 560

 

The value x on the first row of the previous table must be replaced by the respective letter of the unit. Possible values are I: Main unit, S: DI or DO type, or A: Calculation channel. Therefore, cross-referencing row and column allows knowing the valid addressing interval for a module. For example, to select unit 2 (two) and slot 2 (two) the addressing interval for a module is from 121 to 130.

Users can also address all channels from a unit. For example, the value Unit 3: addresses all channels, from 301 to 360. If this interval does not contain all modules, the DA100 module responds with intervals of addresses. The next table contains valid values for each architecture.

Values per architecture

 

Stand-Alone Unit

Expansible Unit

Unit

0 (zero)

I (DA100, main unit) and from 0 (zero) to 5 (five, sub-units DS400 or DS600)

Slot

0 (zero) to 5 (five)

0 (zero) to 5 (five)

Channel or relay

1 (one) to 10. When the channel is equal to 10, add 1 (one) to the current value of the slot and configure the channel or relay with the value 0 (zero)

1 (one) to 10.When the channel is equal to 10, add 1 (one) to the current value of the slot and configure the channel or relay with the value 0 (zero)

 

The next table contains the valid intervals in Yokogawa DA100 Driver for the modules of each DA100 unit.

Input or output channels

Unit

Valid Range

0

001 to 060

1

101 to 160

2

201 to 260

3

301 to 360

4

401 to 460

5

501 to 560

I

601 to 660

S

701 to 760

A

801 to 860

 

The functionality of Yokogawa DA100 Driver commands are subdivided into the following groups:

Effective commands: From 50 to 62

Commands to control execution: From 100 to 104

Commands to request data output: From 150 to 162

Was this page useful?