<< Click to Display Table of Contents >>
Reading Commands |
B1 |
B2 |
B3 |
B4 |
Command |
Size |
Data Type |
|---|---|---|---|---|---|---|
0 (zero) |
0 (zero) |
0 (zero) |
0 (zero) |
Status Request |
32 Elements |
Please check table Elements of the Status Request Block |
2 |
Line |
0 (zero) |
0 (zero) |
Set Point Request |
4 (four) Elements |
Integer. Please check table Elements of the other Blocks |
3 |
Line |
0 (zero) |
0 (zero) |
Amounts Dosed Request |
Integer. Please check table Elements of the other Blocks |
|
7 |
0 (zero) |
0 (zero) |
0 (zero) |
Inventory Request |
Integer. Please check table Elements of the other Blocks |
|
8 |
0 (zero) |
0 (zero) |
0 (zero) |
Warning Request |
String. NOTE: To avoid unnecessary readings on this Block, it is advisable to enable its reading only when Element 6 (six, AminoSys device warnings displayed) of the Status Request Block is equal to 1 (one, turned on) |
NOTE |
It is recommended to read the Status Request Block using a relatively short scan time, between 500 and 1000 ms. An AminoSys device handles it as a disconnection in case it does not receive requests from an HC (Host Computer) within a short period of time, resulting in unnecessary alerts. In addition, reading this Block in a short scan time allows a more precise supervising of this process. |
Elements of the Status Request Block
Element |
Data Type |
Meaning |
|---|---|---|
0 |
Bit |
Line 1 (one) controlled by a Host Computer enabled |
1 |
Bit |
Line 1 (one) busy |
2 |
Bit |
Line 1 (one, batch ready) |
3 |
Bit |
Line 2 (two) controlled by a Host Computer enabled |
4 |
Bit |
Line 2 (two) busy |
5 |
Bit |
Line 2 (two, batch ready) |
6 |
Bit |
AminoSys device warnings being displayed |
7 |
Bit |
Dosage for scale 1 (one) |
8 |
Bit |
Scale 1 (one) empty |
9 |
Bit |
Scale 1's (one) select valve closed |
10 |
Bit |
Scale 1's (one) flushing valve active |
11 |
Integer |
Product dosed for scale 1 (one) |
12 |
Bit |
Coarse dosage for scale 1 (one) |
13 |
Bit |
Fine dosage for scale 1 (one) |
14 |
Bit |
Dosage for scale 2 (two) |
15 |
Bit |
Scale 2 (two) empty |
16 |
Bit |
Scale 2's (two) select valve closed |
17 |
Bit |
Scale 2's (two) flushing valve active |
18 |
Integer |
Product dosed for scale 2 (two) |
19 |
Bit |
Coarse dosage for scale 2 (two) |
20 |
Bit |
Fine dosage for scale 2 (two) |
21 |
Bit |
Product 1's level (1: high level) |
22 |
Bit |
Product 2's level (1: high level) |
23 |
Bit |
Product 3's level (1: high level) |
24 |
Bit |
Product 4's level (1: high level) |
25 |
Bit |
Line 1's (one) waiting bin empty |
26 |
Bit |
Line 1's (one) waiting bin valve open |
27 |
Bit |
Line 2's (two) waiting bin empty |
28 |
Bit |
Line 2's (two) waiting bin valve open |
29 |
Integer |
Active line |
30 |
Bit |
Position of the two-way valve (0: line 1 or 1: line 2) |
31 |
Bit |
Conveying |
NOTE |
Possible values for Bit data types are 0 (zero, turned off) or 1 (one, turned on). |
Element |
Data Type |
Meaning |
|---|---|---|
0 |
Integer |
Product 1 (one) |
1 |
Integer |
Product 2 (two) |
2 |
Integer |
Product 3 (three) |
3 |
Integer |
Product 4 (four) |