PIXIT for Reporting Model

<< Clique para Mostrar o Sumário >>

 

PIXIT for Reporting Model

Y: Supported Service; N: Unsupported Service

ID

Description

Value

Rp1

The supported trigger conditions are (compare PICS)

integrity: Y; data change: Y; quality change: Y; data update: Y; general interrogation: Y

Rp2

The supported optional fields are

sequence-number: Y; report-time-stamp: Y; reason-for-inclusion: Y; data-set-name: Y; data-reference: Y; buffer-overflow: Y; entryID: Y; conf-rev: Y; segmentation: Y

Rp3

Can the server send segmented reports?

Y

Rp4

Mechanism on second internal data change notification of the same analogue data value within buffer period (Compare IEC 61850-7-2 $14.2.2.9)

Send report immediately OR Replace analogue value in pending report

Rp5

Multi client URCB approach (compare IEC 61850-7-2 $14.2.1)

Each URCB is visible to all clients

Rp6

What is the format of EntryID

Based on datetime and sequence number in hex: DDMMYYHHMMSS SEQNUMBER

Rp7

What is the buffer size for each BRCB or how many reports can be buffered

Not explicitly limited, depends on available memory

Rp8

Pre-configured RCB attributes that cannot be changed online when RptEna = FALSE (see also the ICD report settings)

N

Rp9

May the reported data set contain: structured data objects and data attributes?

Y

Rp10

What is the scan cycle for binary events? Is this fixed, configurable

Configurable

Rp11

Does the device support to pre-assign a RCB to a specific client in the SCL

N

Esta página foi útil?