PIXIT for Reporting Model

<< Clique para Mostrar o Sumário >>

 

PIXIT for Reporting Model

Y: Supported Service or N: Unsupported Service

Identifier

Description

Value

Rp1

The supported trigger conditions are (compare PICS)

integrity: Y; data change: Y; quality change: Y; data update: Y; general interrogation: Y

Rp2

The supported optional fields are

sequence-number: Y; report-time-stamp: Y; reason-for-inclusion: Y; data-set-name: Y; data-reference: Y; buffer-overflow: Y; entryID: Y; conf-rev: Y; segmentation: Y

Rp3

Can the server send segmented reports?

Y

Rp4

Mechanism on second internal data change notification of the same analogue data value within buffer period (Compare IEC 61850-7-2 $14.2.2.9)

Send report immediately OR Replace analogue value in pending report

Rp5

Multi client URCB approach (compare IEC 61850-7-2 $14.2.1)

Each URCB is visible to all clients

Rp6

What is the format of EntryID?

Based on date and time and sequence number in hexadecimal DDMMYYHHMMSS SEQNUMBER

Rp7

What is the buffer size for each BRCB or how many reports can be buffered?

Not explicitly limited, depends on available memory

Rp8

Pre-configured RCB attributes that cannot be changed online when RptEna = FALSE. Please check also ICD report settings

N

Rp9

May the reported data set contains structured data objects and data attributes?

Y

Rp10

What is the scan cycle for binary events? Is this fixed, configurable

Configurable

Rp11

Does the device support to pre-assign a RCB to a specific client in the SCL?

N