BACnetNotificationParameters_ChangeOfReliability

<< Clique para Mostrar o Sumário >>

 

BACnetNotificationParameters_ChangeOfReliability

Esta representação de dados complexos via XML é utilizada internamente em outros XMLs suportados pelo driver.

Esquema XML

<xs:complexType name="BACnetNotificationParameters_ChangeOfReliability">
  <xs:sequence>
    <xs:element name="Reliability" type="BACnetReliability" />
    <xs:element name="StatusFlags" type="BACnetStatusFlags" />
    <xs:element name="PropertyValues" type="SequenceOfBACnetPropertyValue" />
  </xs:sequence>
</xs:complexType>

Exemplos

Exemplo 1:

<BACnetNotificationParameters_ChangeOfReliability>
  <Reliability>noFaultDetected</Reliability>
  <StatusFlags>
    <inAlarm>true</inAlarm>
    <overridden>true</overridden>
  </StatusFlags>
  <PropertyValues />
</BACnetNotificationParameters_ChangeOfReliability>

Exemplo 2:

<BACnetNotificationParameters_ChangeOfReliability>
  <Reliability>noSensor</Reliability>
  <StatusFlags>
    <inAlarm>true</inAlarm>
    <overridden>true</overridden>
  </StatusFlags>
  <PropertyValues>
    <BACnetPropertyValue>
      <PropertyIdentifier>action</PropertyIdentifier>
      <PropertyArrayIndex>1237</PropertyArrayIndex>
      <PropertyValue>
        <Boolean>true</Boolean>
      </PropertyValue>
      <Priority>1238</Priority>
    </BACnetPropertyValue>
    <BACnetPropertyValue>
      <PropertyIdentifier>activeVtSessions</PropertyIdentifier>
      <PropertyArrayIndex>1240</PropertyArrayIndex>
      <PropertyValue>
        <Boolean>true</Boolean>
      </PropertyValue>
      <Priority>1241</Priority>
    </BACnetPropertyValue>
    <BACnetPropertyValue>
      <PropertyIdentifier>all</PropertyIdentifier>
      <PropertyArrayIndex>1243</PropertyArrayIndex>
      <PropertyValue>
        <Boolean>true</Boolean>
      </PropertyValue>
      <Priority>1244</Priority>
    </BACnetPropertyValue>
  </PropertyValues>
</BACnetNotificationParameters_ChangeOfReliability>

Esta página foi útil?