FieldId

<< Click to Display Table of Contents >>

 

FieldId

Enum Unique identifier of the column of this Field on an E3Alarm. Possible values for this property are described on the next table.

Possible values for the FieldId property

Value

Column

Description

1

AckRequired

Event needs manual (True) or automatic (False) acknowledgment

2

Acked

Event was acknowledged or not

3

ActorID

Name of the operator that acknowledged this Event

4

ChangeMask

Not used and its value is always equal to 0 (zero)

5

ConditionName

Condition name, in case of an Alarm (Dead Band, Digital, Discrete, Level, or Rate of Change)

6

ConditionActive

Indicates whether the Alarm Source is in Alarm or not

7

Cookie

Value used internally by the Alarm Server

8

Enabled

Determines whether Alarm verification is enabled or not

9

EventCategory

Event category. For Alarms, possible values are Dead Band, Digital, Discrete, Level, or RateOfChange

10

EventType

Type of Event

11

Message

Text configured in the Alarm Source

12

Quality

Quality of the Alarm Source value at the moment of an Event

13

Severity

Value of severity configured in the Alarm Source

14

Source

Expression used to evaluate Alarm conditions

15

SubConditionName

Name of a sub-condition, if this is an Alarm Event

16

EventTime

Date and time of an Event

17

EventTimeUTC

Date and time of an Event, in UTC format

18

CurrentValue

Current value of an Alarm Source, as a floating-point number

19

AlarmArea

Name of an Area to which an Alarm Source belongs

20

AlarmSourceName

Name of an Alarm Source

21

EventTimeMS

Date and time of an Event, in milliseconds

22

InTime

Date and time of entering an Event

23

InTimeMS

Date and time of entering an Event, in milliseconds

24

OutTime

Date and time of leaving an Event

25

OutTimeMS

Date and time of leaving an Event, in milliseconds

26

AckTime

Date and time of acknowledging an Event

27

AckTimeMS

Date and time of acknowledging an Event, in milliseconds

28

FullAlarmSourceName

Full name of an Alarm Source

29

FormattedValue

Formatted value

30

InTimeDbl

Date and time of entering an Event, as a floating-point number

31

OutTimeDbl

Date and time of leaving an Event, as a floating-point number

32

AckTimeDbl

Date and time of acknowledging an Event, as a floating-point number

33

EventTimeDbl

Date and time of an Event, as a floating-point number

34

EventCLSID

Unique identification of an Event

35

ActiveSource

Active Measurement Source of an Alarm Source at the moment of an Event

36

Unbound

Indicates whether an Event is linked to an Alarm Source or not

37

Deleted

Indicates whether an Event was removed or not

38

AllowShelving

Indicates whether an Alarm or Event allows shelving or not

39

Shelved

Indicates whether an Alarm or Event was shelved or not

40

ShelvedTime

Date and time of shelving an Alarm or Event

41

ShelvedOutTime

Date and time of unshelving or 0 (zero) if an Alarm or Event is not yet unshelved

42

ShelveDuration

Duration time, in minutes, that an Alarm or Event has been shelved

43

ShelveMaxDuration

Maximum duration, in minutes, that an Alarm or Event can remain shelved

44

ShelveCount

Number of times an Alarm or Event was shelved

45

ShelveMaxCount

Maximum number of shelvings allowed for an Alarm or Event

46

ShelveActorID

Name of the operator responsible for shelving an Alarm or Event

47

ShelveReason

Reason for shelving an Alarm or Event

48

E3TimeStamp

Date and time of an Event occurrence in Elipse Water format

49

Suppressed

Indicates whether an Alarm was suppressed

50

SuppressedTime

Date and time of suppressing an Alarm

51

SequentialNumber

Sequential number of an Alarm

52

AlarmState

Current status of an Alarm

53

ShelvedExpirationTime

Indicates the programmed date and time for this Alarm or Event to leave its shelving condition

54

OutOfService

Identifies whether an Alarm was suppressed using the Out-of-Service type

55

OutOfServiceTime

Date and time an Alarm was suppressed using the Out-of-Service type

56

ReturnToServiceTime

Date and time in which an Alarm suppressed using the Out-of-Service type returned to normal operation

57

OutOfServiceReason

Reason by which an Alarm was suppressed using the Out-of-Service type by an operator

58

OutOfServiceActorID

Operator that performed the suppression of an Alarm using the Out-of-Service type

Was this page useful?