<< Click to Display Table of Contents >>
AsyncBatchFlushTimeMs |
This property defines the maximum time an asynchronous operation can wait in E3Run before it is sent to an I/O Server. Possible values for this property range between 0 (zero) and 10000 (10 seconds). Values less than 50 use the value of 50 milliseconds. Default value of this property is -1 (minus one), that is, the waiting time is defined in the Maximum Wait Time (milliseconds) option of the Asynchronous Operation Grouping group of the Properties tab of Domain configuration.