Domain, E3 Server, and Hot-Standby

<< Click to Display Table of Contents >>

 

Domain, E3 Server, and Hot-Standby

Fixed the update in executing Domains. When an update in execution was interrupted by another one, some objects could be updated but not active. This bug occurs since v3.0.23.

Now E3 Server restarts in situations of switching or removing the license. In addition, in case it closes due to a license switch with a running Domain, it does not notify the other Hot-Standby server. This bug occurs since v3.0.456.

Fixed the behavior of E3 Server when manually closed during the regressive counting to close or restart by a license switch (it may log the error E00106 incorrectly). This bug occurs since v4.0.87.

Fixed Alarms Summary syncing in Hot-Standby, which was not propagating the events’ EventCLSID field. This bug has occurred since v3.0.109.

Was this page useful?