The configuration parameters to perform a communication with KNX devices are available on this Driver's Properties Window and are described on the next table.
Configuration options for the KNX KNXNet Driver
Tab |
Parameter |
Data Type |
Description |
|---|---|---|---|
Setup |
Physical Layer |
Text |
By default, select the Ethernet option |
Timeout (ms) |
Number |
Defines a limit value for a time-out, in milliseconds, that is, a period this Driver must wait for a valid response from a device |
|
Ethernet |
Transport |
Text |
By default, select the UDP/IP option |
Interface |
Boolean |
Enables using a local Interface, by selecting the IP address of the network card installed on the computer |
|
Main IP |
Text |
IP address of a device, in the format [0-255].[0-255].[0-255].[0-255] |
|
Port |
Number |
By default, use the value 3671 |
NOTE |
If the IP address of a device is unknown, use the multicast IP address 224.0.23.12 in the Main IP option to instruct this Driver to perform an internal Discovery procedure to retrieve the IP address associated with the installed device on the KNXNet/IP network. |