Configuring Properties

<< Click to Display Table of Contents >>

 

Configuring Properties

The configuration parameters to perform a communication with KNX devices are available on this Driver's Properties Window and are described on the next table.

Configuration options for the KNX KNXNet Driver

Tab

Parameter

Data Type

Description

Setup

Physical Layer

Text

By default, select the Ethernet option

Timeout (ms)

Number

Defines a limit value for a time-out, in milliseconds, that is, a period this Driver must wait for a valid response from a device

Ethernet

Transport

Text

By default, select the UDP/IP option

Interface

Boolean

Enables using a local Interface, by selecting the IP address of the network card installed on the computer

Main IP

Text

IP address of a device, in the format [0-255].[0-255].[0-255].[0-255]

Port

Number

By default, use the value 3671

 

NOTE

If the IP address of a device is unknown, use the multicast IP address 224.0.23.12 in the Main IP option to instruct this Driver to perform an internal Discovery procedure to retrieve the IP address associated with the installed device on the KNXNet/IP network.