The next table contains all Datapoint Types from the KNX standard supported by this Driver.

KNX data types

Data Type

Data Subtype

Description

1.xxx (Datapoint Type B1)

001 (Switch)

0: Off or 1: On

002 (Bool)

0: False or 1: True

003 (Enable)

0: Disable or 1: Enable

004 (Ramp)

0: No ramp or 1: Ramp

005 (Alarm)

0: No alarm or 1: Alarm

006 (Binary Value)

0: Low or 1: High

007 (Step)

0: Decrease or 1: Increase

008 (Up Down)

0: Up or 1: Down

009 (Open Close)

0: Open or 1: Close

010 (Start)

0: Stop or 1: Start

011 (State)

0: Inactive or 1: Active

012 (Invert)

0: No inverted or 1: Inverted

013 (Dim Send Style)

0: Start/Stop or 1: Cyclically

014 (Input Source)

0: Fixed or 1: Calculated

015 (Reset)

0: No action (dummy) or 1: Reset command (trigger)

016 (Ack)

0: No action (dummy) or 1: Acknowledge command (trigger)

017 (Trigger)

0 or 1: Trigger

018 (Occupancy)

0: Not occupied or 1: Occupied

019 (Window Door)

0: Closed or 1: Open

021 (Logical Function)

0: Logical OR function or 1: Logical AND function

022 (Scene AB)

0: Scene A or 1: Scene B

023 (Shutter Blinds Mode)

0: Only move Up/Down mode (shutter) or 1: Move Up/Down + StepStop mode (blind)

5.xxx (Datapoint Type U8)

001 (Scaling)

Range: [0..100], Unit: Percent, and Resolution ≈ 0,4%

003 (Angle)

Range: [0..360], Unit: Degrees, and Resolution ≈ 1,4°

004 (Percent U8)

Range: [0..255], Unit: Percent, and Resolution: 1%

005 (Decimal Factor)

Unit: Ratio

006 (Tariff)

0: No tariff available or [1..254]: Current or desired value

010 (Value 1 U Count)

Range: [0..255], Unit: Counter pulses, and Resolution: 1 counter pulse