Tag Reference

<< Click to Display Table of Contents >>

 

Tag Reference

Individual Tags for communication must be used. These Tags are addressed using the Device, N1, N2, and N3 parameters, in the following format:

Device: Panel address (ID), as configured in the file ISECIDMAC.ini

N1: Partition

N2: Zone

N3: Indicates whether synthetic values must be inverted when the zone is greater than 0 (zero)

 

A partition represents a set of zones, there is always at least a partition 0 (zero), and zones are monitoring loops that can be in a failure or trigger state or restored or normalized. The zone 0 (zero) is a special zone that receives general events from a Panel.

The values returned to Tags are based on a number with 4 (four) digits, where the first digit, the most significant one, corresponds to 1 (one) for triggering and 3 (three) for restoring. Possible values are described on the next table.

Failure and restoration codes

Triggering or Failure Code

Meaning

Restoring Code

Meaning

1401

User deactivation

3401

User activation

NA

NA

3456

Partial activation

1130

Zone triggering

3130

Restoration from zone triggering

1133

24h-zone triggering

3133

Restoration from 24h-zone triggering

1146

Quiet triggering

3146

Restoration from quiet triggering

1131

Wired fence triggering

3131

Restoration from wired fence triggering

1371

Cut on detector wiring

3371

Restoration from cut on detector wiring

1372

Short-circuit on detector wiring

3372

Restoration from short-circuit on detector wiring

1383

Detector tamper

3383

Restoration from detector tamper

1333

Problem on bar device

3333

Restoration from problem on bar device

1145

Keyboard tamper

3145

Restoration from keyboard tamper

1570

Temporary nullification of zone

NA

NA

1573

Nullified by triggering

NA

NA

1301

Power failure

3301

Restoration from power failure

1302

Main battery low or short-circuited

3302

Restoration from main battery low or short-circuited

1311

Main battery unavailable or inverted

3311

Restoration from main battery unavailable or inverted

1300

Overload on auxiliary output

3300

Restoration from overload on auxiliary output

1321

Failure or short-circuit on alarm wiring

3321

Restoration from failure or short-circuit on alarm wiring

1351

Phone line failure

3351

Restoration from phone line failure

1384

Low battery of wireless detector

3384

Restoration from low battery of wireless detector

1407

Deactivation via keyboard or phone

3407

Activation via keyboard or phone

1403

Auto-deactivation

3403

Auto-activation

NA

NA

3408

Activation by key

1100

Medical emergency

NA

NA

1110

Trigger or fire panic

3110

Restoration from trigger or fire panic

1121

Coercion password

NA

NA

1122

Quiet panic

NA

NA

1120

Audible or quiet panic

NA

NA

1305

Reset via programming mode

NA

NA

1306

Change on Panel programming

NA

NA

1354

Failure to communicate events

NA

NA

1461

Incorrect password

NA

NA

1410

Remote access using download or upload application

NA

NA

1413

Download failure

NA

NA

1601

Manual test

NA

NA

1602

Recurring test

NA

NA

1616

Maintenance request

NA

NA

1621

Reset of event buffer

NA

NA

1624

Event log full

NA

NA

1625

Date and time were reset

NA

NA

1147

Failure on Smart supervising

3147

Restoration from Smart supervising

1422

PGM triggering

3422

PGM un-triggering

1322

Reception signal

NA

NA

1531

NA

3531

Device found

1360

Failure of GPRS Keep Alive

3360

Restoration from failure of GPRS Keep Alive

1361

Failure of Eth Keep Alive

3361

Restoration from failure of Eth Keep Alive