Active Data

<< Click to Display Table of Contents >>

 

Active Data

Read-Only

 

B1

Identifier stored on a device's memory

B2

23, which corresponds to table 23

B3

0 (zero)

B4

0 (zero)

 

The Elements of this Block Tag are described on the next table.

Elements of Block Tag Active Data

Element

Description

1

Pressure

2

Temperature

3

Current value of Zb

4

Current value of Z

5

Current value of CF

6

Uncorrected flow rate, or ql

7

Corrected flow rate, or qn

8

Current status. Please check the next table for information about the bits of this Element

9

Latched status. Please check the next table for information about the bits of this Element

10

Unlatched counter status. Please check the next table for information about the bits of this Element

11

Unlatched output status. Please check the next table for information about the bits of this Element

12

Unlatched display status. Please check the next table for information about the bits of this Element

13

Latched display status. Please check the next table for information about the bits of this Element

14

Current average for pressure. This value is equal to 0 (zero) if the average calculation is turned off and this value is redefined at the end of this calculation's duration

15

Last average for pressure. At the end of the average's calculation, the current average is copied to this register

16

Current average for temperature. This value is equal to 0 (zero) if the average calculation is turned off and this value is redefined at the end of this calculation's duration

17

Last average for temperature. At the end of the average's calculation, the current average is copied to this register

18

K (Z ÷ Zb)

 

Meaning of bits from Elements from 8 (eight) to 13

Bit

Meaning

0

High pressure alarm

1

Low pressure alarm

2

Over-range pressure error

3

Zero-pressure error

4

High temperature alarm

5

Low temperature alarm

6

Maximum temperature error

7

Minimum temperature error

8

Low battery

9

Input alarm

10

O/P1 pulse alarm

11

O/P2 pulse alarm

12

Incomplete O/P pulse

13

Not used

14

Not used

15

Default pressure in use

16

Default temperature in use