PIXIT for Control Model

<< Click to Display Table of Contents >>

 

PIXIT for Control Model

Y: Supported Service; N: Unsupported Service

ID

Description

Value

Ct1

What control modes are supported

status-only: Y; direct-with-normal-security: Y; sbo-with-normal-security: Y; direct-with-enhanced-security: Y; sbo-with-enhanced-security: Y

Ct2

Is the control model fixed, configurable or online changeable?

Configurable and online changeable

Ct3

Is Time activated operate (operTm) supported?

N

Ct4

Is operate-many supported?

N

Ct5

Will the DUT activate the control output when the test attribute is set in the SelectWithValue or Operate request (when N test procedure Ctl2 is applicable)?

N

Ct6

What are the conditions for the time (T) attribute in the SelectWithValue or Operate request?

DUT ignores the time and execute the command as usual

Ct7

Is pulse configuration supported?

N

Ct8

What is the behaviour of the DUT when the check conditions are set. Is this behaviour fixed, configurable, or online changeable?

DUT ignores the check value

Ct9

What additional cause diagnosis are supported?

Blocked-by-switching-hierarchy: Y/N; Select-failed: Y/N; Invalid-position: Y/N; Position-reached: Y/N; Parameter-change-in-execution: Y/N; Step-limit: Y/N; Blocked-by-Mode: Y/N; Blocked-by-process: Y/N; Blocked-by-interlocking: Y/N; Blocked-by-synchrocheck: Y/N; Command-already-in-execution: Y/N; Blocked-by-health: Y/N; 1-of-n-control: Y/N; Abortion-by-cancel: Y/N; Time-limit-over: Y/N; Abortion-by-trip: Y/N

Ct10

How to force a test-not-ok respond with SelectWithValue request?

 

Ct11

How to force a test-not-ok respond with Select request?

 

Ct12

How to force a test-not-ok respond with Operate request?

 

Ct13

Which origin categories are supported?

 

Ct14

What happens if the orCat value is not supported?

 

Ct15

Does the IED accept a SelectWithValue or Operate with the same ctlVal as the current status value?

 

Ct16

Does the IED accept a select or operate on the same control object from two different clients at the same time?

 

Ct17

Does the IED accept a Select or SelectWithValue from the same client when the control object is already selected (tissue 334)?

SBOns: Y; SBOes: Y

Ct18

Is for SBOes the internal validation performed during the SelectWithValue or Operate step?

SelectWithValue: Y; Operate: Y; SelectWithValue and Operate: Y

Ct19

Can a control operation be blocked by Mod=Off or Blocked?

N

Ct20

Does the IED support local or remote operation?

N

Ct21

Does the IED send an InformationReport with LastApplError as part of the Operate response- for control with normal security?

SBOns: N; Dons: N