PIXIT for Control Model |
Y: Supported Service; N: Unsupported Service
ID |
Description |
Value |
---|---|---|
Ct1 |
What control modes are supported |
status-only: Y; direct-with-normal-security: Y; sbo-with-normal-security: Y; direct-with-enhanced-security: Y; sbo-with-enhanced-security: Y |
Ct2 |
Is the control model fixed, configurable or online changeable? |
Configurable and online changeable |
Ct3 |
Is Time activated operate (operTm) supported? |
N |
Ct4 |
Is operate-many supported? |
N |
Ct5 |
Will the DUT activate the control output when the test attribute is set in the SelectWithValue or Operate request (when N test procedure Ctl2 is applicable)? |
N |
Ct6 |
What are the conditions for the time (T) attribute in the SelectWithValue or Operate request? |
DUT ignores the time and execute the command as usual |
Ct7 |
Is pulse configuration supported? |
N |
Ct8 |
What is the behaviour of the DUT when the check conditions are set. Is this behaviour fixed, configurable, or online changeable? |
DUT ignores the check value |
Ct9 |
What additional cause diagnosis are supported? |
Blocked-by-switching-hierarchy: Y/N; Select-failed: Y/N; Invalid-position: Y/N; Position-reached: Y/N; Parameter-change-in-execution: Y/N; Step-limit: Y/N; Blocked-by-Mode: Y/N; Blocked-by-process: Y/N; Blocked-by-interlocking: Y/N; Blocked-by-synchrocheck: Y/N; Command-already-in-execution: Y/N; Blocked-by-health: Y/N; 1-of-n-control: Y/N; Abortion-by-cancel: Y/N; Time-limit-over: Y/N; Abortion-by-trip: Y/N |
Ct10 |
How to force a test-not-ok respond with SelectWithValue request? |
|
Ct11 |
How to force a test-not-ok respond with Select request? |
|
Ct12 |
How to force a test-not-ok respond with Operate request? |
|
Ct13 |
Which origin categories are supported? |
|
Ct14 |
What happens if the orCat value is not supported? |
|
Ct15 |
Does the IED accept a SelectWithValue or Operate with the same ctlVal as the current status value? |
|
Ct16 |
Does the IED accept a select or operate on the same control object from two different clients at the same time? |
|
Ct17 |
Does the IED accept a Select or SelectWithValue from the same client when the control object is already selected (tissue 334)? |
SBOns: Y; SBOes: Y |
Ct18 |
Is for SBOes the internal validation performed during the SelectWithValue or Operate step? |
SelectWithValue: Y; Operate: Y; SelectWithValue and Operate: Y |
Ct19 |
Can a control operation be blocked by Mod=Off or Blocked? |
N |
Ct20 |
Does the IED support local or remote operation? |
N |
Ct21 |
Does the IED send an InformationReport with LastApplError as part of the Operate response- for control with normal security? |
SBOns: N; Dons: N |