[N] and [B] Parameters of Block or PLC Tags

<< Click to Display Table of Contents >>

 

[N] and [B] Parameters of Block or PLC Tags

Use a PLC or Block Tag to read or write data to a PLC memory.

 

N1/B1

Not used

N2/B2

Data type. For more information, please check topic Data Types

N3/B3

Point address, usually starting at 1 (one)

N4/B4

Maximum number of characters, in case of a String data type (N1 equal to 27 or 28)

 

NOTE

As the structure of GE SRTP protocol allocates a maximum of 200 bytes for a data area, please check topic Maximum Number of Elements per Block Tag for the maximum number of Elements a Block Tag supports, according to the type of data to process.