<< Click to Display Table of Contents >>
[N/B] Addressing Parameters of PLC and Block Tags (Writing) |
N1/B1 |
Index for the PLC address, configured on Driver Settings Window |
N2/B2 |
Command in TANN format, in which T is the data type (please check topic Data Types), A is the command type (hundreds, please check topic Command Types), and NN is the command (tenths and units, please check topic Writing Commands) |
N3/B3 |
Starting address for writing |
N4/B4 |
Starting bit for writing if data type is Bit or String size if data type is String |