Cyclic Request

<< Click to Display Table of Contents >>

 

Cyclic Request

Read-Only

 

B1

23

B2

Not used

B3

Not used

B4

Not used

Size

Between 6 (six) and 9 (nine)

 

This Tag returns a Block Tag with 6 (six) or 9 (nine) Elements. This size depends on the value of a meter's ProgV variable, in which a value greater or equal to 5 (five) returns a Block Tag with 9 (nine) Elements or otherwise with 6 (six) Elements. The values returned in this Tag are the following:

•Status of a meter, a bit field with a size of 16:

•Bit 0: New blackout value

•Bit 1: New phase number value

•Bit 2: New value of malfunctioning

•Bit 3: Communication via optical head for configuration

•Bit 4: Not used

•Bit 5: Communication via optical head for reading

•Bit 6: No load

•Bit 7: Meter exposed to a magnetic field

•Bit 8: End of integration period

•Bit 9: End of a day

•Bit 10: End of a month

•Bit 11: End of a year

•Bit 12: Time correction in progress

•Bit 13: Time correction limit reached

•Bit 14: Invalid array of user-defined constants

•Bit 15: Clock malfunctioning

•Index of a period: 1 (one) to 60 minutes, 2 (two) to 30 minutes, and 4 (four) to 15 minutes. To get a numerical value in seconds, use the Integration Period Tag

•Type of a meter

•Sec variable

•ProgV variable

•Battery supply

 

If a meter's ProgV variable is greater or equal to 5 (five), the following bit fields are also transmitted:

•Variable of KtrU number factor

•Variable of KtrI number factor

•Exponent variable of number factor