Cyclic Request |
B1 |
23 |
B2 |
Not used |
B3 |
Not used |
B4 |
Not used |
Size |
Between 6 (six) and 9 (nine) |
This Tag returns a Block Tag with 6 (six) or 9 (nine) Elements. This size depends on the value of a meter's ProgV variable, in which a value greater or equal to 5 (five) returns a Block Tag with 9 (nine) Elements or otherwise with 6 (six) Elements. The values returned in this Tag are the following:
•Status of a meter, a bit field with a size of 16:
•Bit 0: New blackout value
•Bit 1: New phase number value
•Bit 2: New value of malfunctioning
•Bit 3: Communication via optical head for configuration
•Bit 4: Not used
•Bit 5: Communication via optical head for reading
•Bit 6: No load
•Bit 7: Meter exposed to a magnetic field
•Bit 8: End of integration period
•Bit 9: End of a day
•Bit 10: End of a month
•Bit 11: End of a year
•Bit 12: Time correction in progress
•Bit 13: Time correction limit reached
•Bit 14: Invalid array of user-defined constants
•Bit 15: Clock malfunctioning
•Index of a period: 1 (one) to 60 minutes, 2 (two) to 30 minutes, and 4 (four) to 15 minutes. To get a numerical value in seconds, use the Integration Period Tag
•Type of a meter
•Sec variable
•ProgV variable
•Battery supply
If a meter's ProgV variable is greater or equal to 5 (five), the following bit fields are also transmitted:
•Variable of KtrU number factor
•Variable of KtrI number factor
•Exponent variable of number factor