Collecting and Storing Files in COMTRADE Standard

<< Click to Display Table of Contents >>

 

Collecting and Storing Files in COMTRADE Standard

If the process of collecting files is enabled in a Pextron profile, this Driver follows these steps:

1.When starting this Driver, a random time between 0 (zero) and 13 minutes starts counting, and then tries to perform a collect process. If this collect process is successful, this file is saved and its existence is indicated by the DNPADD.-33.0.X Tag. The number of files left for transfer is indicated by the DNPADD.-33.1.X Tag.

2.The application can write to the DNPADD.-33.2.X Tag to request a new immediate collect process or to DNPADD.-33.3.X Tag to request a new collect process after a random time. In both cases the collect process is performed regardless of DNPADD.-33.1.X Tag indicating 0 (zero) or more collect processes to transfer.

3.If no Tag is written, this Driver does not perform a new collect process.

 

Configuration of channels, directory, and file name must be performed before starting a collect process.

Was this page useful?