trendLogMultiple.loggingType

<< Click to Display Table of Contents >>

 

trendLogMultiple.loggingType

According to the BACnet protocol documentation:

Specifies whether the Trend Log Multiple object collects log records using polling or triggered acquisition. COV Logging is not allowed for a Trend Log Multiple object.

Property loggingType of object trendLogMultiple can be read and written using a single IOTag.

Text Parameters

Property

Value

ParamDevice

<deviceAddress>

ParamItem

trendLogMultiple-<objectAddress>.loggingType

Numeric Parameters

Property

Value

N1:

<deviceAddress>

N2:

<type> = 27

N3:

<objectAddress>

N4:

<property> = 197

Tag Value

An integer representing one of the options of enumeration <BACnetLoggingType>.

Was this page useful?