<< Click to Display Table of Contents >>
pulseConverter.count |
According to the BACnet protocol documentation:
Indicates the count of the input pulses as acquired from the physical input or the property referenced by the Input_Reference property.
Property count of object pulseConverter can be read and written using a single IOTag.
Property |
Value |
ParamDevice |
<deviceAddress> |
ParamItem |
pulseConverter-<objectAddress>.count |
Property |
Value |
N1: |
<deviceAddress> |
N2: |
<type> = 24 |
N3: |
<objectAddress> |
N4: |
<property> = 177 |
A 32-bit unsigned integer.